The unit cooler

QH type AW

Quote inquiry

제품사진
Features
  • Designed for medium and large Warehouse to Refrigerate and Freeze
  • Efficiency is increased by using Ø15.88 inner grooved tube.
  • Pipe pitch: R43.3 x S50mm
  • Increased the efficiency of cold air flow by use axial fan
  • Ceiling mount type or installing floor type
  • Power supply : 3Ph, 220V/380V, 50Hz/60Hz
  • Refrigerant : R-22(standard), Other refrigerants are available(option)

Specification table
SPEC. MODEL ROOM
TEMP
FIN
PITCH
(mm)
T.AREA
(㎡)
COOLING CAPACITY (Kcal/h) FAN MOTOR
(Ø x W x P x EA)
AIR
VOLUME
(CMM)
WATER DEFROST DEFROST HEATER
(kWxEA)
CONNECTION TUBE
(Ø mm)
WEIGHT
(Kg)
TD 10℃ TD 7℃ TD 5℃ WATER
(ℓ/min)
WATER
IN
DRAIN
OUT
DRAIN FAN GUIDE IN OUT
QH 150
AW
M -10 6.5 117.2 24630 13190 8250 550 x 1.5 x 4 x 2 290 90 40 65 1.72 0.52 22.22 41.28 470
L -25 6.5/8.5 104 21860 11700 7360 105 460
F -40 10 99.2 20850 11170 6980 145 500
QH 200
AW
M -10 6.5 134.5 28540 15350 9610 550 x 1.5 x 4 x 2 290 105 50 80 1.92 0.52 22.22 41.28 510
L -25 6.5/8.5 134.3 28980 15500 9850 140 540
F -40 10 113.9 23910 12820 8020 165 550
QH 250
AW
M -10 6.5 151.4 31950 16490 10850 550 x 1.5 x 4 x 2 290 120 50 80 1.92 0.52 22.22 41.28 540
L -25 6.5/8.5 172.1 35020 18750 11750 165 570
F -40 10 153.7 32300 17300 10820 220 610
QH 300
AW
M -10 6.5 184.4 38110 20760 13010 600 x 2.2 x 4 x 2 390 140 65 100 2.12 0.52 22.22 53.98 600
L -25 6.5/8.5 188.8 40180 21500 13590 190 620
F -40 10 187.3 38110 20550 12950 220 680
QH 350
AW
M -10 6.5 222.4 44100 24500 15110 550 x 1.5 x 4 x 3 435 160 65 100 2.52 0.53 22.22 53.98 690
L -25 6.5/8.5 227.6 47760 25630 16040 225 720
F -40 10 225.9 44830 24220 15600 310 790
QH 400
AW
M -10 6.5 249.5 51520 28600 17620 600 x 2.2 x 4 x 3 585 187 65 100 2.72 0.53 28.58 66.68 740
L -25 6.5/8.5 255.4 53670 28750 18120 252 800
F -40 10 253.4 53250 28525 17840 367 870
QH 450
AW
M -10 6.5 283 59110 31750 11920 600 x 2.2 x 4 x 3 585 215 65 100 3.12 0.53 28.58 66.68 830
L -25 6.5/8.5 281.4 58370 32300 19620 275 2.82 840
F -40 10 287 60230 32280 20200 415 3.12 940

blue : Use in a normal condition (If used in the other condition then has to be asked)

※ Specifications and photo should be changed without any notice for improvement.