Condensing unit

PA-type Panasonic for medium and low temperatures

Quote inquiry

제품사진

Specification table

Panasonic , for medium and low temperatures

Type. Model PA050 SMF PA075 SMF PA100 SMF PA150 SMF PA200 SMF
호칭출력 5HP (3.7KW) 7HP (5.5KW) 10HP (7.5KW) 15HP (11KW) 20HP (15KW)
Power Supply Main 3PH 220V/380V 60Hz
Control 1PH 220V 60Hz
Used refrigerant R-22
Refrigeration ability (Kcal/h)
ET ℃
※ CT : 50 ℃
-5℃ 10825 15064 22415 30987 44899
-10℃ 8865 12699 18193 25201 37006
-15℃ 7102 10515 14462 20076 29955
-20℃ 5572 8521 11203 15614 23773
-30℃ 3095 5099 6148 8607 13912
-40℃ 1427 2390 3078 4153 7420
Comp. Model C-L37M9H C-L55M9D C-L75M9I C-L113M9I C-L150M9I
Start current 61.4 95.3 105 136 198
Operating current 10 15.3 21.2 29.3 43.8
Discharge rate 21.95 ㎥/h 30.67 ㎥/h 47.67 ㎥/h 63.42 ㎥/h 88.73 ㎥/h
oil type Suniso 3GS, Shell Clavus G68
Volume 2.8 3 5.2 5.2 5.2
Crankcase heater 1PH 220V 70W 1PH 220V 70W 1PH 220V 100W 1PH 220V 100W 1PH 220V 100W
Cond. Heat exchanger type Fin & Tube
Condenser model PA 050 PA 075 PA 100 PA 150 PA 200
Fan Fan dia(Φ x EA) 400 x 2 500 x 2 500 x 2 600 x 2 630 x 2
Power(KW x EA) 0.1 x 2 0.2 x 2 0.2 x 2 0.4 x 2 0.75 x 2
Air volume(CMM) 80 140 140 280 380
Receiver Volume(L) 7.6 10 15 26 41
Fusible Plug Φ4.5 (73℃)
Condenser pressure control High Pressure Switch
Protections High, Low Pressure Switch, Compressor Thermo Limiter
Components Filter Drier, Sight Glass, Flexible Tube, Liquid Pipe Valve, Oil Separater, Accumulator, Pressure gauge (high pressure, low pressure, oil pressure - except PA030 ~ PA200), gauge (high, low, oil - PA030 ~ PA200 excluded), Solenoid Velve (Option)
Connection Pipe (Φ) Gas Inlet Φ22.22 Φ28.58 Φ28.58 Φ34.92 Φ41.28
Liq. Outlet Φ12.7 Φ15.88 Φ15.88 Φ22.22 Φ22.22
External Dimension L 1240 1330 1330 1660 1860
W 60 790 790 840 935
H 1413 1453 1453 1653 1704
Anchor Dimension ( L` x W` ) 850 x 500 940 x 690 940 x 690 1270 x 740 1480 x 835
Weight(Kg) ≒280 ≒390 ≒420 ≒530 ≒620

◆ It is necessary to apply the condenser one step higher when manufacturing for air conditioning.

※ Specification and photos should be changed without any notice for improvement.